SIVACON 8PT (SIEMENS)

Block diagram of the application of the cabinets SIVACON

Technology SIVACON 8PT –is a new module solution of the distribution systems, designed by the world-renowned producer, which allow to fulfill any requirements of the Customer to the distribution and to execute maintanance, repair and to replace the cabinet’s elements, without a shutdown of the whole device.
Cabinets SIVACON8PT are used for the electrical energy distribution with a voltage up to 690V, AC current up to 7400A. They can be used in the all production areas, energy transmission and distribution

Application diagram of the cabinets SIVACON

Application areas of  SIVACON:

  • electric power plants
  • distribution cabinets for buildings and structures
  • distribution substations
  • main distribution boards and auxiliary electrical systems for energetics, chemical, oil, gas industry and other branches.
SIVACON-struct

Characteristics

Summary table

Norms and Regulations Typical combinations of the low-voltage switching devices. Check of behavior during the internal accidents
(localization capability)
Earthquake resistance
IEC 60439-1, DIN EN 60439-1, (VDE 0660 Part500)

IEC 61641, VDE 0660 Part500, Appendix 2

IEC 60068-3-3, IEC 60068-2-57, IEC 60980, KTA 2201/4

Air gaps and
and leakage distances
Rated impulse withstand voltage (Uimp)

Overvoltage category

Pollution degree

8kV

III

3

Rated insulation voltage (Ui) 1000V
Rated operation voltage (Ue) Up to 690V
Rated current (In)
Bus bars  (3- and 4-pole)
Main horizontal bus bars Rated current up to 7400A
Rated impulse withstand  current (Ipk) up to 375kА
Rated short-time withstand current (Icw) up to 150kА, 1sec up to 120kА, 3sec
Vertical bus bars for the power circuit breakers Rated current up to 6300A
Rated impulse withstand  current (Ipk) up to 250kА
Rated short-time withstand current (Icw) up to 80kА, 3sec; up to 100kА, 1sec
Vertical bus bars for the hard wiring of the structural elements Rated current up to 1400A
Rated impulse withstand  current (Ipk) up to 163kА
Rated short-time withstand current (Icw) up to 65kА*, 1sec; up to 50kА, 3sec
Vertical bus bars for the plug-in structural elements Rated current up to 1200A
Rated impulse withstand  current (Ipk) up to 163kА
Rated short-time withstand current (Icw) up to 65kА*, 1sec; до 50kА, 3sec
Vertical bus bars for the drawout structural elements Rated current up to 1200A
Rated impulse withstand  current (Ipk) up to 163kА
Rated short-time withstand current (Icw) up to 65kА*, 1sec
up to 50kА, 3sec
Rated currents of the devices Power circuit breaker up to 6300А
Outgoing feeders up to 630А
Internal division From the form 1 to the form 4 IEC 60439-1, segment 7.7, DIN EN 60439-1
Exterior surface processing Door

 

frame

 

housing

Galvanization / powder coating /wet coating

Galvanization / powder coating /wet coating

Powder coating /wet coating

Protection level Up to IEC 60529, EN 60529 IP 30 up to IP 54
Dimensions Height:

Width:
Depth:

2200, 2600mm (with the additional upper compartment)
400, 600, 800, 1000, 1200mm
600, 800, 1000, 1200mm
* conventional rated short-circuit current Iсс up to 100 kА

Cabinet’s design

SIVACON adapts to Customer requirements

Structurally cabinets SIVACON 8PT can be divided into 5 sections:
1 – compartment of the device
2 – compartment of the horizontal bus bars
3 – compartment of the cable inlet
4 – compartment of the secondary circuits
5 – cable compartment for the cable connection from backside or from above.

A module technology gives the opportunity of optimal adaptation of SIVACON to any requirements.

SIVACON-sections

Key features of SIVACON:

  • type tested standard combinations of the devices (ТТА)
  • standard position of the bus bars in the upper or back part of the cabinet
  • 3 and 4 pole bus bar system for the current up to 7400 А
  • rated impulse withstand current Ipk up to 375 kA
  • a deep compartment for multi-purpose installation
  • modular structure of the device’s compartment
  • one-sided or back-to-back installation
  • cable inlet from above or from the backside
  • any components can be installed into the compartment, independently of the bus bar position and cabinet’s depth.
  • specific task-oriented internal space division degrees from the form 1 to the form 4 (IEC 60439-1)
  • deep compartment of the devices

Optimal adaptation to the indoor space conditions:

  • installation near the wall, or free-standing devices
  • cables or buses can be connected from above or from the backside
  • cable compartment is placed from the front or from the backside
  • easy access to the buses

Frame and case

SIVACON-carcas

КFrame of the cabinets SIVACON 8PT can be made with the welded or bolt joint of the components.
Frame components and cabinet’s cases are made from the sheet steel with the following thickness:
− frame — 2,5 mm;
− housing — 2,0 mm.
Surface treatment:
− powder coating;
− galvanization.
Perforation holes are made all over the whole perimeter in increments of 25 mm.
The door opens 180°.
Spring-loaded secure lock protects from self-opening from the doors.
The excess pressure is released through the upper cover of the cabinet.
Level of protection according to GOST 14254—96, IEC 60529:
− IP30, IP31, IP40, IP41, IP42 — cabinets with the natural ventilation of the cabinets;
− IP30, IP31, IP40, IP41, IP42, IP54 — nonaerated cabinets.

Cabinet’s frame. The view from above

sivacon top look

Busbar system

Busbars in the cabinets SIVACON 8PT are placed in the separate closed compartment, access to them is available only through the steel end caps, which are bolted to the frame of the cabinet.
Busbars are invisible and aren’t available when the doors and end caps are open for the access to the other elements of the cabinets SIVACON 8PT.
Cabinets of SIVACON 8PT are provided with 3-phase buses of the power supply:
А (L1), В (L2), С (L3),

А (L1), В (L2), С (L3), neutral working bus N (or combined neutral working bus and neutral protective bus PEN) and also neutral protective bus PE.

Main characteristics of the bus bars

Type Rated current In*, А Rated short-time withstand current (Icw), kА Rated surge current (Ipk), kА
Bus bars up to 3200А
dlinaya shina non Aerated cabinets 2400 80 200
aerated cabinets 3200
Bus bars up to 4000А
shina non Aerated cabinets 2400 100 250
aerated cabinets 3200
Bus bars up to 7400А
dvoynaya shina non Aerated cabinets 2400 150 375
aerated cabinets 3200

Form of internal division

SIVACON allows to fulfill forms of internal division from the form 1 to the form 4 according to IEC 60439-1.

Form1

1 – Housing
2 – Internal division
3 – Bus bars, including distribution buses
4 – Functional unit, including connection point

Form 1 – no internal division

Form2a

Form 2 – division of bus bars and funktional units

Form2a

Form 2а
No division between clamps for outer conductors and bus bars

Form2b

Form 2b
Division between clamps for outer conductors and bus bars

Form 3 – Division of bus bars and funktional units + division of funktional units from each other + division between clamps for outer conductors and bus bars

Form3a

Form 3а
No division between clamps for outer conductors and bus bars

Form3b

Form 3b
Division between clamps for outer conductors and bus bars

Form 4 – division of bus bars and funktional units + division of funktional units among themselves + division between clamps for outer conductors and bus bars

Form4a

Form 4а
Clamps of outer conductors aren’t separated from the connected funktional unit

Form4b

Form 4b
Clamps of outer conductors are separated from the connected funktional unit

Cabinets of the FCB1 and BC types

shkafy FCB1 i BC

Cabinets of the FCB1 and BC type are provided with the air-break switches of the 3WL type  produced by SIEMENS with the rate current from 630А up to 6300А and are applied as:

  • entrance cabinet
  • cabinets of power supply for feeders
  • sectional cabinets

Automatic circuit breaker is installed into the separate compartment of the box. A front panel of the automatic circuit breaker goes through the door’s cut out and is available for management and maintenance. Depending on the cabinet’s configuration the door can be as general as for every cabinet’s compartment.
There are 2 installation methods of the automatic circuit breaker 3WL possible:

  • fixed performance  — automatic circuit breaker is fixed in the cabinet
  • draw out  performance — automatic circuit breaker is installed into the basket with the draw out device, which is fixed in the cabinet.

Secondary circuit equipment is placed in the compartment of additional cabinet’s equipment.

Versions of the cabinet’s structures with the air-break switches 3WL according to the type of connection. Cable connection from the front

Connecting cables from the front 630А — 6300А

Cable connection from backside 630А — 3200А

Cabinets of the OFW type (draw out type of module)

shkaf OFW

Cabinet for the cable feeders or drive with the draw out modules assures high ease of use and optimal safety and high level of the device readyness. Quick repalcement and module modernization are possible due to appliance of the draw-out principle . Any module can be additionally supplied or replaced.
The draw out construction SIVACON assures the highest level of equipment readiness.
A vertical bus system for the plug-in contacts goes through in the back side of the cabinet and is protected against contacts by a special housing (IP20).

Versions of the cabinet’s structures with the draw-out modules according to the type of connection.

A draw-out module is a combination of the low-voltage switching devices (automatic circuit breaker, contactor, relay), which are used for the energy distribution (cable feeder) or for the equipment’s electromotor control (motor feeder). This equipment is placed on the wiring board inside the draw out module. On the front of the draw out module can be placed the control devices (control buttons, signal lamps) and measuring instruments (ampere-meter, voltmeter).
Depending on the content of the equipment and its size draw out modules are distinguished by height: 100mm, 150mm, 200mm, 300mm, 400mm, 500mm and 600mm.

vykatnoy modul 100mm

100mm height draw out module (motor feeder)

As a rule draw out modules are provided with the electronic control and motor protection relay SIMOCODE PRO produced by SIEMENS, which consists of: basic module, current and voltage measuring modules, operator panel, expansion modules: digital I/O, analog input, earth-fault module.  In this case electromotor control is carried out according to the throwaway code included to the basic module both in the standalone mode and in the PROFIBUS DP net.

komplekt eletr rele

Set of the electronic control and motor protection relays SIMOCODE PRO

Draw out modules SIVACON assure the safe use and changes.

In the cabinets draw out modules can be installed in the following positions:

  • operating position
  • position  «TEST»
  • “off” position.
Operating position position  «TEST»; “off” position
rabochee pologeniye pologeniye test pologeniye vyklyuchennoe
1 raboch 2 test 3 vykl
sylov kontakty – power contacts
kontakty upravl – control contacts

Cabinets of the OFPM type (plug-in modules)

shkaf OFPM

Cabinet for cable feeders or motor with the plug-in modules is a cost-effective alternative of the cabinets with the draw out modules. Quick module  replacement without a shutdown of the cabinet is possible due to the plug-in contacts on the supply side. Any module can be additionally supplied or replaced. Plug-in structure SIVACON assures excellent savings, reliability and flexibility. Vertical bus system for the plug-in contacts goes through in the back side of the cabinet and is protcted against contacts by a special housing (IP20).

Versions of the cabinet’s structures wth the plug-in modules.

Without an additional door of the cable compartment

With an additional door of the cable compartment

A plug-in module is a combination of the low-voltage switching devices (automatic circuit breaker, contactor, relay), which are used for the energy distribution (cable feeder) or for the equipment’s electromotor control (motor feeder). This equipment is placed on the wiring board inside the plug-in module. On the cabinet’s door are placed the control devices (control buttons, signal lamps) and measuring instruments (ampere-meter, voltmeter).

Depending on the content of the equipment and its size the plug-in modules are distinguished by height: 75mm, 125mm, 175mm, 275mm, 375mm

75mm vperedi 75mm szadi
75mm height plug-in module
(moto feeder). Front view
75mm height plug-in module
(moto feeder). Back view
125mm vperedi 125mm szadi
125mm height plug-in module
(moto feeder). Front view
175mm height plug-in module
(moto feeder). Front view

Cabinets of the PFC type (reactive power compensation)

Reactive power compensation cabinet PFC is used for reactive energy compensation and keeping of power factor (cos ϕ) on the target level; this reduces load on the transformers and cables, transmission losses and cost of electricity. Cabinets consist of the separate compensation modules, which allows to add step by step the rated power of the compensation device.
On/off control of the condenser is carried out by the special programmable controller produced by MODL, Germany.

Шкафы типа PFC (компенсация реактивной мощности)

Compensation module consists of: protection device (fuses, automatic circuit breakers), contactors with contacts of the advanced switching and current limiting resistors and condensers.

Depending on the load type in the electric circuits of the consumer compensation cabinets can be with and without trottle.

Compensation cabinets without trottle are used for the centralized compensation of the reactive power  in the linear electronic circuits. Maximal power of the one cabinet without trottle can be equal to 500kVar.

Compensation cabinets with trottle are used for the centralized compensation of the reactive power  in the  nonlinear electronic circuits (>20% from total load). Maximal power of the one cabinet with  trottle 5.67%  can be equal to 400kVar, with trottle 7% — 300 kVаr.

Nonthrottleable cabinet 500 kVar

Throttleable cabinet 400 kVar

Дросселируемый шкаф 400кВар

Cabinets of the CCS type (free-design cabinets)

Free-design cabinets are used for installation in them of different components and can be used for solving of different tasks. For example, for placement of controllers, or frequency inverters, a lot of low-power consumer devices etc.
Cabinets can have different configuration:
with and without main busbar;
with and without vertical busbar;
with one or several wiring boards.
Cable connection is performed from the front of the cabinet.

Testing of cabinets

abinets SIVACON 8PT and combinations of the switching devices have been tested in the laboratory and have passed type tests and this ensures the maximal reliability and the personnel safety.
Cabinets SIVACON 8PT have passed tests for compliance with IEC 60439-1, DIN EN 60439-1 (VDE 0660 часть 500).

Type tests:

  • test for temperature limit
  • insulation resistance check
  • closed-circuit fault tolerance check
  • test for correct wiring between the combination bodies of switching devices and the grounding conductor according to the results of the resistance check or measuring
  • check for closed-circuit fault tolerance of the grounding conductor
  • check of creepage distances and air gaps
  • mechanical integrity testing
  • IP protection level testing

Every power distribution device SIVACON passes the following types of testing before shipping:

  • a visual monitoring of production, including wiring works, and functional tests on electrical equipment if required
  • insulation resistance check
  • check of protective measures and visual monitoring of the end to end ground lines.

Our experience in designing systems using the SIMATIC PCS7

JSC “AzovElectroStal”

2012

ACS TP DSV-5. Design, delivery

ООО “Каргилл”, РФ (г.Ефремов)

2012

Автоматическая система управления линией участка переработки лауриновых тропических жиров. Проект, поставка

ЧАО “Завод Полупроводников”, г.Запоржье, Украина

2011

АСУ ТП склада ТХС

ЧАО “Завод Полупроводников”, г.Запорожье, Украина

2011

АСУ ТП цеха нейтрализации

Centrotherm для ЧАО “Завод Полупроводников”, г.Запорожье, Украина

2011

АСУ ТП VGR (Vent Gas Recovery). Проект, наладка

Company Arikom“, China

2011

ACS TP production of titanium spongeproject

JSC “Plant of Semiconductors“, Zaporozhye, Ukraine

2011

ACS TP the PAC production (polysilicon). Design, delivery, commissioning

Company “Yunnan Chaotuo Titanium Industry Co., Ltd”, China

2011

ACS TP Production of titanium sponge. “project

JSC “Plant of Semiconductors“, Zaporozhye, Ukraine

2010

ACS TP production of TCS (TCS). Design, delivery, commissioning

Company “Panzhihua Iron and Steel”, China

2010

ACS TP production of titanium sponge capacity of 15000t / y. “Redistributions from 1 to 9. The project, commissioning

JSC ZTMK”, Zaporozhye, Ukraine

2009 Plot chlorine production vapors. project

JSC “Plant of Semiconductors“, Zaporozhye, Ukraine

2008

Process control system for hydrogen productionDesign, delivery, commissioning

Company “Pan’gang Group Steel City Enterprises”, China

2008

ACS TP production of purified TiCl4 capacity of 25,000 t / year for the production of titanium dioxide pigment. “Queue 2project

Company “Pan’gang Group Steel City Enterprises”, China

2008 ACS TP production of purified TiCl4 capacity of 25,000 t / year for the production of titanium dioxide pigment. “Queue 1. project

Siemens Oil & Gas Offshore AS, Norway

2008 The project to upgrade Snorre A SAS. Modernization of automated platforms Oil & Gas Snorre A with S5 toPCS7

JSC “AzovElectroStal“, Mariupol

2008 Automated process control system for steel refining in the installation Ladle PK-60.” post 2

JSC “AzovElectroStal“, Mariupol

2008 Automatic control system for the introduction of doping materials and additives to the furnace DSP-60 andbucketpost 2

Metallurgical Combine SINOSTEEL, China

2007 Automated control system of technological process of production of ferronickel

Siemens Oil & Gas Offshore AS, Norway

2007 The project to modernize the Oseberg SAS. Modernization of automated platforms Oil & Gas Oseberg withTeleperm to PCS7

JSC “AzovElectroStal“, Mariupol

2006 Automated process control system for steel refining in the installation Ladle PK-60.” post 1